Vaillant aroTHERM plus for Commercial Heat Pump Projects

Vaillant's aroTHERM plus R290 platform has moved from premium domestic to credible light-commercial deployment up to 320 kW. Here is how it stacks up for Irish projects in 2026.

By Smart Solar Editorial · Updated 18 May 2026 · 11 min read

Vaillant's commercial moment

Vaillant Group — headquartered in Remscheid, Germany, with Irish distribution through Vaillant Ireland in Dublin — has historically been a domestic and light-commercial specialist. The aroTHERM plus platform, launched 2019 with R290 (propane) as standard refrigerant, has progressively moved up the capacity ladder. By 2026, Vaillant Ireland offers credible commercial cascade configurations to 320 kW total capacity through stacked aroTHERM plus units.

This matters because R290 has become the F-gas-future-proof refrigerant of choice for many Irish commercial buyers — and Vaillant's aroTHERM plus is the most mature, most-installed R290 platform in the European market. Vaillant Ireland reported approximately 4,200 aroTHERM plus units installed across the island by end-2025, with about 280 of those in commercial configurations (sites with multiple units cascaded).

The aroTHERM plus platform

Single-unit aroTHERM plus specifications (current 2026 catalogue):

  • Capacity range: 3.5 kW to 28 kW per unit
  • Refrigerant: R290 (propane), GWP 3
  • Flow temperature: up to 75 °C single-stage at A–7
  • SCOP (EN 14825 Average, W35): up to 5.1
  • SCOP (EN 14825 Average, W55): up to 3.7
  • Sound power: 49 dB(A) at typical operating conditions
  • Refrigerant charge per kW: approximately 0.07 kg/kW

Cascade configurations stack multiple outdoor units in parallel feeding a common buffer tank. Vaillant Ireland's commercial cascade specifications:

  • 2-unit cascade: up to 56 kW (typical for medium offices, GP surgeries, small care homes)
  • 4-unit cascade: up to 112 kW (medium care homes, primary schools)
  • 8-unit cascade: up to 224 kW (large care homes, secondary schools)
  • 12-unit cascade: up to 320 kW (large commercial buildings)

Why R290 is the unique value proposition

The aroTHERM plus's R290 refrigerant delivers three commercially meaningful advantages:

1. F-gas regulation future-proofing

R290's GWP of 3 places it permanently below the EU F-gas thresholds. There is no service refrigerant scarcity scenario through 2050. For 20–25 year commercial assets, this is materially better than R32 or R454B which face progressive quota tightening through 2030.

2. High flow temperature without cascade penalty

Single-stage R290 delivers 70–75 °C flow temperatures at A–7 (cold winter day). This is roughly 15–20 °C higher than R32 or R454B systems can manage single-stage. Practical implications for Irish commercial retrofits:

  • Legacy radiator systems can be retained without resizing
  • DHW pasteurisation cycles can be delivered without electric top-up
  • Buffer tank temperatures can be raised, reducing storage volume requirements
  • Combined SCOP improves 15–25% versus electric-assisted R32 alternatives

3. Refrigerant cost stability

R290 retails at €8–€12/kg in May 2026 versus R32 at €45–€60/kg and R410A at €120–€180/kg. Refrigerant cost is becoming a meaningful lifecycle consideration for commercial heat pumps; R290 effectively immunises the asset against this risk.

Sizing aroTHERM plus for Irish commercial projects

Indicative aroTHERM plus cascade sizing for common Irish commercial configurations:

  • GP medical centre, 1,200 m²: 2-unit cascade, 56 kW (with DHW for hand-washing, sterilisation)
  • 40-bed care home, 1,800 m²: 4–5 unit cascade, 110–140 kW
  • Primary school, 1,600 m²: 4-unit cascade, 90–110 kW (DHW limited so simpler design)
  • 60-bed care home, 2,800 m²: 8-unit cascade, 200–230 kW
  • Small office building, 2,000 m²: 4-unit cascade, 100–120 kW

Above approximately 320 kW total demand, aroTHERM plus cascade becomes operationally complex (12+ units to manage) and most Irish projects switch to larger single-unit platforms — Vaillant's own larger commercial range or competitor platforms from Daikin, Mitsubishi or Carrier.

Cascade hydraulic design

A successful aroTHERM plus cascade depends on hydraulic design:

  • Low-loss header or common buffer is essential — direct-coupled cascades suffer from flow imbalance and short-cycling
  • Buffer volume sizing: typically 30–50 litres per kW of cascade capacity, so a 200 kW cascade needs 6,000–10,000 litres of buffer
  • Variable-speed primary pumps to match cascade output to building demand
  • Cascade controller (Vaillant multiMATIC 700 or vrnetDIALOG 870) manages stage rotation, lead-lag and fault recovery

A typical 200 kW Irish care home aroTHERM plus cascade includes:

  • 8 × aroTHERM plus 25 kW outdoor units (with one spare per N+1 convention)
  • 8,000 litre stratified buffer tank
  • Twin variable-speed primary pumps
  • Cascade controller plus building BMS integration
  • F-gas leak detection (R290 requires gas detection in confined plant rooms)

R290 safety and installation

R290's A3 flammability classification (highly flammable) is the most common objection from Irish facilities managers and HSE risk assessors. Vaillant's design response substantially neutralises the risk:

  • Outdoor monobloc construction — all refrigerant contained in the hermetic outdoor unit
  • No indoor refrigerant pipework — heat is transferred via water circuits only
  • Sealed refrigerant circuits with no field joints
  • Very low charge per kW (~0.07 kg/kW)
  • Hermetic compressor with no shaft seals

For multi-unit cascade installations placed outdoors with 1 m clearance to building openings, R290 risk assessment under Irish HSE guidance typically requires:

  • 1.5 m clearance to ignition sources (fire dampers, electrical equipment)
  • ATEX-rated electrical isolators within 1.5 m of refrigerant circuit
  • Annual visual inspection of refrigerant circuit integrity
  • Documented F-gas (in this case, hydrocarbon) management plan

Most Irish commercial aroTHERM plus deployments comply with these requirements through standard outdoor installation practice.

2026 installed pricing

Indicative installed pricing for aroTHERM plus cascade configurations in Ireland in 2026:

  • 2-unit cascade (56 kW): €38,000–€58,000 installed
  • 4-unit cascade (112 kW): €72,000–€110,000 installed
  • 8-unit cascade (224 kW): €145,000–€220,000 installed
  • 12-unit cascade (320 kW): €215,000–€330,000 installed

These figures include outdoor units, hydraulic buffer, primary pumps, controls and commissioning. They exclude distribution upgrade and electrical supply works.

Pricing is roughly comparable to equivalent capacity from Daikin or Mitsubishi air-to-water ranges, but the refrigerant future-proofing case has shifted procurement preferences increasingly toward Vaillant in 2024–2026.

Vaillant Ireland installer network

Vaillant Ireland accredits approximately 90 commercial installers across the island. Commercial cascade work is typically delivered by larger Tier-1 partners including:

  • Aircontrol Ireland — Dublin commercial heat pump specialist
  • Heat Pumps Ireland — Cork and Munster commercial
  • Solar Plus Energy — Galway and West region
  • Greenfield Renewables — Northeast commercial

Vaillant Ireland provides:

  • 5-year warranty on aroTHERM plus units, extendable to 7 years with annual service
  • Vaillant Connect remote monitoring as standard
  • Spares network from Dublin distribution centre with next-day delivery
  • Commercial cascade design support direct from Vaillant Ireland's technical team

Notable Irish aroTHERM plus commercial projects

  • Beneavin House Dublin nursing home: 8-unit aroTHERM plus 25 kW cascade (200 kW total)
  • Coláiste Choilm Ballincollig: 4-unit cascade (110 kW) integrated with school PV
  • St Vincent's GP Surgery network: 2–3 unit cascades across 14 Dublin surgeries
  • Marymount University Hospital Cork: 12-unit cascade (320 kW) for hospice extension

Choosing aroTHERM plus

For Irish commercial projects in 2026, aroTHERM plus is the right specification when:

  • Total capacity is in the 50–320 kW range
  • R290 refrigerant future-proofing is a procurement priority
  • High flow temperature is required (DHW pasteurisation, legacy radiators)
  • Outdoor monobloc plant room location is acceptable
  • Multi-unit cascade complexity is manageable (suits projects with strong on-site facilities management)

It's the wrong choice for projects requiring:

  • Indoor plant location (R290 charge limits restrictive)
  • Above 320 kW total capacity (switch to larger single-unit platforms)
  • Multi-zone refrigerant-side control (VRV/VRF preferable)
  • Simultaneous heating and cooling (Carrier or VRV preferable)

Outlook

Vaillant's pipeline through 2026–2027 includes a larger 60 kW aroTHERM plus variant (in development, target launch Q4 2026) which would meaningfully simplify cascade design for projects in the 200–400 kW range. The platform's R290 leadership position is increasingly being recognised in EXEED-funded Irish projects, where the refrigerant choice strengthens the project's long-term carbon and resilience profile.

For Irish commercial buyers in 2026 where R290 is a strategic preference, aroTHERM plus remains the most mature and well-supported platform available.

Get 3 free commercial heat pump quotes — free and no obligation.

Frequently asked questions

What is the maximum capacity of a Vaillant aroTHERM plus cascade?

Up to 320 kW total via 12-unit cascade of 25 kW aroTHERM plus outdoor units. Above this, project complexity (cascade controls, hydraulic balancing) typically argues for switching to larger single-unit platforms from Daikin, Mitsubishi or Carrier.

Is R290 propane safe for commercial care home installations?

Yes, when installed outdoors as hermetic monobloc units with no indoor refrigerant pipework. R290 is A3 (highly flammable) but the very low charge per kW (~0.07 kg/kW), sealed circuit construction and outdoor placement substantially neutralise the risk. Irish HSE risk assessment typically requires 1.5 m clearance to ignition sources and annual circuit inspection.

What SCOP does Vaillant aroTHERM plus deliver in Irish conditions?

Up to SCOP 5.1 at W35 underfloor heating, dropping to SCOP 3.7 at W55 to standard radiators. In field operation on Irish care homes and offices, SPF 3.5–4.2 is typical depending on flow temperature design. The R290 platform's ability to deliver 70 °C single-stage avoids the SCOP penalty of electric-assisted DHW pasteurisation.

How much does a Vaillant cascade cost for an Irish care home?

Indicative 2026 installed pricing: 4-unit cascade (112 kW) at €72k–€110k for a small care home, 8-unit cascade (224 kW) at €145k–€220k for a medium care home. Includes outdoor units, buffer tank, cascade controller and commissioning. EXEED grant typically captures 28–30% on care home oil-replacement projects.

Sources & further reading