R32, R290 and R454B: Commercial Heat Pump Refrigerants for Ireland
EU F-gas Regulation 2024/573 is squeezing high-GWP refrigerants out of the Irish commercial heat pump market. Here is how R32, R290 and R454B stack up for procurement decisions taken today.
By Smart Solar Editorial · Updated 18 May 2026 · 11 min read
The F-gas squeeze is now reshaping Irish procurement
EU Regulation 2024/573 (the new F-gas Regulation, in force since 11 March 2024) has accelerated the phasedown of HFCs across the European refrigeration and heat pump market. By the time Irish commercial buyers are placing 2026 orders, three refrigerants dominate the credible shortlist:
- R32 — single-component HFC, GWP 675, the current commercial workhorse
- R454B — HFC/HFO blend, GWP 466, increasingly the spec for new VRV/VRF in 2026–2028
- R290 (propane) — natural refrigerant, GWP 3, the long-term winner above 2030
Older refrigerants — R410A (GWP 2088), R134a (GWP 1430), R407C (GWP 1774) — are now uneconomic to specify because of F-gas quota constraints and the EU's hard-banned GWP thresholds.
What the F-gas Regulation actually requires
EU 2024/573 introduces a series of hard cut-offs that bite directly on commercial heat pump procurement:
- From 1 January 2025: stationary self-contained equipment with GWP ≥ 150 banned (already in force)
- From 1 January 2027: split air-to-water heat pumps below 12 kW must use GWP < 150 refrigerant
- From 1 January 2029: split air-to-water heat pumps 12–50 kW must use GWP < 150
- From 1 January 2032: all split heat pumps below 12 kW must use GWP < 150
- From 1 January 2033: all single-split air conditioners below 12 kW must use GWP < 150
- From 2035: centralised AC and chiller equipment below 12 kW under hard restrictions
- HFC quota phasedown: virgin HFC supply cut to 5% of 2015 baseline by 2036
The practical consequence for Irish commercial specifiers is that any new install in 2026 should be future-proofed against the 2030–2035 service refrigerant scarcity. That means avoiding R410A entirely, treating R32 as a 10-year service horizon, and seriously evaluating R290 for any plant intended to operate beyond 2035.
R32 — the current default
R32 (difluoromethane) is the single-component HFC that replaced R410A across most of the residential and light-commercial market from 2018. Key characteristics:
- GWP: 675 (well above the 150 threshold for future-proofing)
- Flammability class: A2L (mildly flammable)
- Operating pressure: similar to R410A, allowing legacy compressor and pipework designs
- Charge per kW: roughly 0.2–0.3 kg/kW thermal
- Irish availability: excellent — Daikin, Mitsubishi, LG, Samsung, Panasonic all offer R32 commercial product through Irish distribution
R32 remains the dominant refrigerant in Irish commercial heat pumps up to 100 kW in 2026. Above 100 kW, R454B and R290 are taking share.
R454B — the bridge refrigerant
R454B is a blend of R32 (68.9%) and R1234yf (31.1%), engineered to reduce GWP while preserving R410A-equivalent operating characteristics. Key characteristics:
- GWP: 466 (still above 150 but materially better than R32)
- Flammability class: A2L
- Operating pressure: very close to R410A, enabling drop-in compressor designs
- Charge per kW: similar to R32
- Irish availability: growing rapidly — Carrier AquaForce 2 series and several Trane chillers ship with R454B as standard from 2024
R454B is increasingly the specification for 50–500 kW commercial chiller-heat-pump duties in 2026, particularly where the OEM has not yet brought a hydrocarbon line to market.
R290 — the long-term winner
R290 (propane) is a natural hydrocarbon refrigerant with a GWP of 3 — effectively zero from an F-gas regulation perspective. Key characteristics:
- GWP: 3
- Flammability class: A3 (highly flammable)
- Operating pressure: lower than R32/R410A, requires purpose-designed compressors
- Charge per kW: very low, typically 0.05–0.1 kg/kW thermal
- Flow temperature capability: up to 75 °C single-stage, ideal for retrofits onto existing radiator circuits
- Irish availability: growing — Vaillant aroTHERM plus, Viessmann Vitocal 250-A, Mitsubishi Ecodan R290, Bosch Compress 7800i AW all available through Irish distribution
R290's A3 flammability classification is the main objection, but the engineering response (charge limits, monolithic hermetic refrigerant circuits, outdoor placement, no indoor refrigerant pipework, ATEX-rated electrical compartments) has largely neutralised the risk for outdoor monobloc applications. Indoor installations and split systems remain harder to certify.
Which refrigerant for which application
A 2026 Irish commercial specification matrix:
- Outdoor monobloc, 30–100 kW, retrofit: R290 — best efficiency, future-proof, high flow temperature capability
- Outdoor monobloc, 100–300 kW, new build: R290 if a tier-1 unit is available, otherwise R454B
- VRV/VRF, 50–500 kW, multi-tenant office or hotel: R32 or R454B (R290 not yet practical for VRV due to charge limits)
- Centralised chiller-heat-pump, 250 kW–2 MW: R454B from Carrier or Trane; R1234ze for higher-temperature applications
- Industrial process heat, 75–95 °C flow: R290, R1234ze or R744 (CO₂) cascade
Procurement clauses worth including
For any commercial heat pump tender in 2026, request the following from each bidder:
- Refrigerant designation and GWP
- F-gas regulation compliance statement against 2027, 2029 and 2032 thresholds
- Available refrigerant supply forecast through 2035
- Service refrigerant retail price for the past 24 months
- Manufacturer commitment to refrigerant supply continuity through end of warranty period
Tier-1 OEMs (Daikin Ireland, Mitsubishi Electric Ireland, Carrier Ireland, Vaillant Ireland) will provide all of these as standard. If a bidder cannot, the lifetime risk profile is materially higher.
Service and disposal cost reality
F-gas refrigerant prices have moved sharply on quota constraint. Irish service refrigerant pricing in May 2026:
- R32: €45–€60/kg (up from €18/kg in 2022)
- R454B: €70–€90/kg
- R290: €8–€12/kg (effectively unconstrained as a natural refrigerant)
- R410A: €120–€180/kg (scarcity pricing on recovered material only)
A 250 kW commercial heat pump with a 25 kg refrigerant charge represents €1,500–€2,250 in R32, but €3,000+ on a future quota-constrained day. R290's price stability is now a material capex consideration on its own.
The bottom line for Irish 2026 procurement
Default to R290 for any new outdoor monobloc commercial heat pump if a tier-1 product is available. Use R454B for VRV and centralised chiller duty where R290 is not yet practical. Accept R32 only if neither alternative is available and the asset has a credible refrigerant retrofit pathway. Avoid R410A entirely. This positioning protects you against the 2027–2032 F-gas thresholds and shields the project from the worst of the HFC quota volatility.
Get 3 free commercial heat pump quotes — free and no obligation.
Frequently asked questions
Will R32 be banned in Ireland?
Not banned outright, but heavily restricted. From January 2027 split heat pumps below 12 kW cannot use refrigerants with GWP > 150 (R32 is 675). From January 2029 the limit extends to 12–50 kW splits. R32 service refrigerant will become progressively more expensive through 2030 as HFC quota tightens.
Is R290 (propane) safe for commercial heat pumps?
Yes, when installed outdoors as a sealed monobloc unit with no indoor refrigerant piping. R290 is classed A3 (highly flammable) but charge limits, hermetic circuit design and outdoor placement neutralise the risk. Indoor installations and splits remain technically harder. Tier-1 outdoor units from Vaillant, Viessmann, Mitsubishi and Bosch are certified for Irish commercial use.
What refrigerant should I specify for a 2026 hotel heat pump?
For VRV serving multiple zones, R454B is the current best balance of availability and future-proofing. For centralised plant feeding LPHW radiators or underfloor heating, R290 is preferable where a tier-1 monobloc is available. Avoid R32 above 50 kW unless the OEM commits to refrigerant supply through 2035.
How much does refrigerant cost for a commercial heat pump?
A 250 kW commercial heat pump holds roughly 25 kg of refrigerant. At May 2026 Irish prices that is €1,500–€2,250 in R32, €1,750–€2,250 in R454B, or €200–€300 in R290. Refrigerant price stability is increasingly a procurement criterion in its own right.
Sources & further reading
- EU Regulation 2024/573 on Fluorinated Greenhouse Gases — EUR-Lex
- EPA Ireland - F-gases — EPA Ireland
- ASHRAE Designation and Safety Classification of Refrigerants — ASHRAE 34