EU Ecodesign Requirements for Commercial Heat Pumps

EU Ecodesign sets the minimum efficiency floor for commercial heat pumps placed on the Irish market. Here is what the latest thresholds mean for 2026 procurement.

By Smart Solar Editorial · Updated 18 May 2026 · 10 min read

What Ecodesign actually does

The EU Ecodesign Directive (2009/125/EC, with subsequent product-specific regulations) sets minimum mandatory efficiency requirements for energy-related products placed on the EU market. For commercial heat pumps, three regulations matter:

  • Regulation (EU) 813/2013 — space heaters and combination heaters (up to 400 kW)
  • Regulation (EU) 2016/2281 — air heating, cooling and high-temperature process chillers
  • Regulation (EU) 206/2012 — air conditioners (including heat pumps up to 12 kW)

In parallel, Energy Labelling Regulations set mandatory information disclosure (the familiar A++ to G energy labels) and require manufacturer registration in the EU's EPREL database before products can be placed on the market.

For Irish commercial heat pump procurement, Ecodesign and Energy Labelling work together to:

  1. Filter out the worst-performing products from the market (Ecodesign minimum thresholds)
  2. Standardise efficiency declaration so buyers can compare bids (Energy Labelling SCOP/SEER)
  3. Provide a single authoritative database for product verification (EPREL)
  4. Drive market upgrade through periodic threshold tightening

Current 2026 Ecodesign thresholds

The most recent threshold revision (2023, applied from January 2024) set the following minimums for commercial heat pumps:

Air-to-water heat pumps (≤ 400 kW)

  • Low-temperature (W35): SCOP ≥ 3.5 (climate Average)
  • Medium-temperature (W55): SCOP ≥ 2.8
  • Off-mode losses: ≤ 1 W
  • Sound power: depends on capacity, typically 60–75 dB(A)

Water-to-water heat pumps (≤ 400 kW)

  • Low-temperature (W35): SCOP ≥ 4.0 (climate Average)
  • Medium-temperature (W55): SCOP ≥ 3.4

Air-to-air heat pumps (≤ 12 kW)

  • Heating SCOP: ≥ 4.6 (climate Average, A++ minimum for sale)
  • Cooling SEER: ≥ 6.1

Process chillers (≥ 12 kW)

  • SEPR (Seasonal Energy Performance Ratio for Process): minimum varies by category
  • Glycol process duty: SEPR ≥ 5.0 for ≤ 400 kW

The next Ecodesign threshold revision is scheduled for January 2027, with expected SCOP minimums rising by approximately 0.3–0.5 across most categories. Manufacturers must redesign or withdraw products that fall below the new thresholds.

The EPREL database

Since 2021, all energy-related products placed on the EU market must be registered in the EPREL (European Product Registry for Energy Labelling) database before sale. For Irish commercial heat pump buyers, EPREL is the authoritative source for:

  • Declared SCOP and SEER values
  • Refrigerant type and GWP
  • Sound power level
  • Tested capacity
  • Manufacturer technical files

Critically, the EPREL declaration must match what is on the energy label and the product datasheet. Discrepancies can be reported to the European Commission and trigger enforcement.

For commercial heat pump procurement, the disciplined approach is:

  1. Identify the proposed model
  2. Look up the EPREL entry by manufacturer or model number
  3. Verify SCOP, refrigerant and capacity match the supplier's bid
  4. Retain the EPREL extract in the procurement audit file

EPREL is searchable at https://eprel.ec.europa.eu/ and provides public access without registration.

Ecodesign and EXEED interaction

The SEAI Triple-E Register — which determines ACA capital allowance eligibility — typically sets criteria 10–15% above the Ecodesign minimum. For example:

  • Ecodesign minimum air-to-water at W35: SCOP 3.5
  • Triple-E minimum air-to-water at W35: SCOP 4.0 (approximately)
  • EXEED-preferred target at W35: SCOP 4.2+

This means an Ecodesign-compliant product may not be Triple-E listed and therefore may not qualify for ACA. For EXEED-funded projects, always specify Triple-E registered equipment, not just Ecodesign-compliant.

Sound power labelling

Ecodesign requires manufacturer declaration of sound power level in dB(A). For commercial heat pumps in Ireland, sound power labelling drives several procurement decisions:

  • Outdoor placement acoustic assessment uses the declared sound power
  • Local Authority planning conditions typically reference declared sound power
  • Acoustic enclosure specification is sized from declared sound power
  • EXEED documentation requires sound power evidence

Typical declared sound power for Tier-1 commercial heat pumps:

  • 50 kW air-to-water: 58–68 dB(A) sound power
  • 150 kW air-to-water: 65–75 dB(A)
  • 250 kW VRV outdoor unit: 70–78 dB(A)
  • 500 kW central chiller: 78–85 dB(A)

Sound power is not the same as sound pressure at receptor. Pressure at receptor reduces with distance and directionality, typically 15–25 dB(A) lower than source sound power at 10 m distance.

High-temperature process heat pumps

The 2024 Ecodesign threshold revision specifically addresses high-temperature heat pumps capable of delivering 70 °C+ flow temperatures. Minimum SEPR for high-temperature process duty:

  • 70 °C flow temperature: SEPR ≥ 2.8
  • 85 °C flow temperature: SEPR ≥ 2.3
  • 95 °C flow temperature: SEPR ≥ 1.9

These thresholds make industrial process heat pumps a credible mainstream procurement option for Irish pharma, food and beverage manufacturing in 2026, where previously the technology was too inefficient to compete with gas boilers above 70 °C.

Refrigerant disclosure

Energy Labelling Regulations require refrigerant type and GWP disclosure on the product label and in EPREL. This information feeds into:

  • F-gas regulation compliance planning
  • CSRD and EU Taxonomy reporting
  • EXEED carbon impact calculations

For Irish commercial buyers, refrigerant disclosure is now a mandatory procurement filter. Bids that fail to provide refrigerant type and GWP do not meet basic regulatory transparency standards and should be rejected.

Energy Labelling for commercial scale

The familiar A++ to G energy labels apply directly only to products below 70 kW. For commercial heat pumps above 70 kW, a "package label" methodology applies — the heat pump is labelled in combination with the heating system architecture (radiators, UFH, FCUs, controls) it serves.

The package label methodology recognises that a heat pump's real-world efficiency depends heavily on the distribution system temperature. A heat pump rated A++ with W35 underfloor heating will deliver dramatically better real-world performance than the same heat pump with W65 legacy radiators.

For procurement, the practical consequence is that the heating system designer (typically the MEP consultant) must produce a package label calculation for buildings above 70 kW combined load. This calculation feeds the BER (via NEAP) and informs the EXEED design submission.

Verification and market surveillance

Ecodesign and Energy Labelling are enforced in Ireland by:

  • Competition and Consumer Protection Commission (CCPC) for general products
  • SEAI for energy-related products including heat pumps
  • EPA for refrigerant-related disclosures

Market surveillance includes:

  • Random product testing through independent laboratories
  • Documentation audits at retailer and installer level
  • EPREL database consistency checking
  • Cross-referencing energy labels with installed equipment

Non-compliance penalties under S.I. No. 489/2020 European Union (Ecodesign Requirements for Energy-Related Products) Regulations include fines up to €500,000 per product type and prohibition on sale.

Outlook through 2030

The Ecodesign and Energy Labelling framework is on a steady trajectory of tightening thresholds:

  • 2027: Next major Ecodesign revision with ~0.4 SCOP increase across categories
  • 2029: Expected introduction of GWP-based minimum thresholds in Ecodesign (independent of F-gas regulation)
  • 2030: Likely revised Energy Labelling scale (A to G with new A threshold above current A++)
  • 2032: Anticipated minimum SCOP 4.0 for low-temperature commercial heat pumps

For Irish commercial buyers, the implication is that today's "best in class" product specification (Tier-1 SCOP 4.2+ at W35) is likely the new Ecodesign minimum by 2032. Specifying significantly above current minimums is the route to procurement future-proofing.

Practical compliance for Irish commercial procurement

  1. Verify EPREL listing for every proposed heat pump model
  2. Cross-check declared SCOP against EPREL and supplier datasheet
  3. Confirm Triple-E listing for ACA capital allowance qualification
  4. Retain the energy label / package label in the project audit file
  5. Use declared sound power for acoustic planning and assessment
  6. Specify Ecodesign 2027 thresholds for future-proofing on long-life assets

Ecodesign is a baseline, not a stretching standard. For Irish commercial heat pump projects with 20–25 year asset lives, procurement that just meets the current minimum will fall below the regulatory standard within the asset life. Spec above the minimum, document the package label, and verify through EPREL.

Get 3 free commercial heat pump quotes — free and no obligation.

Frequently asked questions

What is the minimum SCOP for an EU Ecodesign compliant heat pump?

From January 2024: SCOP 3.5 minimum for low-temperature air-to-water (W35), SCOP 2.8 for medium-temperature (W55), SCOP 4.0 for low-temperature water-to-water. Air-to-air below 12 kW requires SCOP 4.6. The next threshold revision in January 2027 is expected to raise these by 0.3–0.5.

What is the EPREL database?

European Product Registry for Energy Labelling — the EU's authoritative database of all energy-related products placed on the market. Manufacturers must register heat pumps before sale, declaring SCOP, SEER, refrigerant type, GWP, sound power and capacity. Searchable at eprel.ec.europa.eu without registration. Procurement best practice is to verify every proposed heat pump model against its EPREL entry.

Does Ecodesign apply to commercial heat pumps above 70 kW?

Yes. Ecodesign minimum efficiency requirements apply across the commercial range. Energy Labelling above 70 kW uses a 'package label' methodology that labels the heat pump in combination with the heating system distribution (radiators, UFH, FCUs). The MEP consultant produces the package label calculation, which feeds BER and EXEED documentation.

Is Ecodesign the same as Triple-E?

No. Triple-E (SEAI Register for ACA eligibility) typically sets criteria 10–15% above Ecodesign minimums. An Ecodesign-compliant product may not qualify for ACA capital allowance. For Irish commercial projects seeking ACA, always specify Triple-E registered equipment, not just Ecodesign-compliant.

Sources & further reading